5. COMMUNICATION IDENTIFIER
IMCD06-E2
33
īš„ Input range table
Thermocouple input
Code
Input type
Input Range
0 to 200 °C K 01
K 0 to 400 °C K 02
0 to 600 °C K 03
0 to 800 °C K 04
0 to 1000 °C K 05
0 to 1200 °C K 06
0 to 1372 °C K 07
0 to 100 °C K 13
0 to 300 °C K 14
0 to 450 °C K 17
0 to 500 °C K 20
0 to 800 °F K A1
0 to 1600 °F K A2
0 to 2502 °F K A3
20 to 70 °F K A9
0 to 200 °C J 01
J 0 to 400 °C J 02
0 to 600 °C J 03
0 to 800 °C J 04
0 to 1000 °C J 05
0 to 1200 °C J 06
0 to 450 °C J 10
0 to 800 °F J A1
0 to 1600 °F J A2
0 to 2192 °F J A3
0 to 400 °F J A6
0 to 300 °F J A7
0 to 1600 °C *1 R 01
R 0 to 1769 °C *1 R 02
0 to 1350 °C *1 R 04
0 to 3200 °F *1 R A1
0 to 3216 °F *1 R A2
0 to 1600 °C *1 S 01
S 0 to 1769 °C *1 S 02
0 to 3200 °F *1 S A1
0 to 3216 °F *1 S A2
400 to 1800 °C B 01
B 0 to 1820 °C *1 B 02
800 to 3200 °F B A1
0 to 3308 °F *1 B A2
0 to 800 °C E 01
E 0 to 1000 °C E 02
0 to 1600 °F E A1
0 to 1832 °F E A2
0 to 1200 °C N 01
N 0 to 1300 °C N 02
0 to 2300 °F N A1
0 to 2372 °F N A2
-199.9 to +400.0 °C *2 T 01
T -199.9 to +100.0 °C *2 T 02
-100.0 to +200.0 °C T 03
0.0 to 350.0 °C T 04
-199.9 to +752.0 °F *2 T A1
-100.0 to +200.0 °F *2 T A2
-100.0 to +400.0 °F *2 T A3
0.0 to 450.0 °F T A4
0.0 to 752.0 °F T A5
W5Re/ 0 to 2000 °C W 01
W26Re 0 to 2320 °C W 02
0 to 4000 °F W A1
Code
Input type
Input Range
0 to 1300 °C A 01
PL II 0 to 1390 °C A 02
0 to 1200 °C A 03
0 to 2400 °F A A1
0 to 2534 °F A A2
-199.9 to +600.0 °C *2 U 01
U -199.9 to +100.0 °C *2 U 02
0.0 to 400.0 °C U 03
-199.9 to +999.9 °F *2 U A1
-100.0 to +200.0 °F *2 U A2
0.0 to 999.9 °F U A3
0 to 400 °C L 01
L 0 to 800 °C L 02
0 to 800 °F L A1
0 to 1600 °F L A2
RTD input
Code
Input type
Input Range
-199.9 to +649.0 °C D 01
Pt100 -199.9 to +200.0 °C D 02
-100.0 to +50.0 °C D 03
-100.0 to +100.0 °C D 04
-100.0 to +200.0 °C D 05
0.0 to 50.0 °C D 06
0.0 to 100.0 °C D 07
0.0 to 200.0 °C D 08
0.0 to 300.0 °C D 09
0.0 to 500.0 °C D 10
-199.9 to +999.9 °F D A1
-199.9 to +400.0 °F D A2
-199.9 to +200.0 °F D A3
-100.0 to +100.0 °F D A4
-100.0 to +300.0 °F D A5
0.0 to 100.0 °F D A6
0.0 to 200.0 °F D A7
0.0 to 400.0 °F D A8
0.0 to 500.0 °F D A9
-199.9 to +649.0 °C P 01
JPt100 -199.9 to +200.0 °C P 02
-100.0 to +50.0 °C P 03
-100.0 to +100.0 °C P 04
-100.0 to +200.0 °C P 05
0.0 to 50.0 °C P 06
0.0 to 100.0 °C P 07
0.0 to 200.0 °C P 08
0.0 to 300.0 °C P 09
0.0 to 500.0 °C P 10
Voltage input and Current input
Code
Input type
Input Range
0 to 5 V DC 4 01
0 to 10 V DC
*
5 01
1 to 5 V DC 0.0 to 100.0 % 6 01
0 to 20 mA DC 7 01
4 to 20 mA DC 8 01
*
Z-1010 specification
*1: 0 to 399 °C/0 to 799 °F: Accuracy is not guaranteed.
*2: -199.9 to -100.0 °C/-199.9 to -158.0 °F : Accuracy is not guaranteed.