EasyManua.ls Logo

Rockwell Automation Allen-Bradley Micro830

Rockwell Automation Allen-Bradley Micro830
390 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 2080-UM002N-EN-E - November 2022 369
Appendix H User-defined Function Block Motion Instructions
Table 112 - MAM Operands
Operand Type Format Description
_EN BOOL Tag True when the rung is enabled.
Ref_Ctrl_Cfg_In raC_UDT_Itf_K5100_Cfg Tag Interface from device object.
Ref_Ctrl_Set_In raC_UDT_Itf_K5100_Set Tag Interface from device object.
Ref_Ctrl_Cmd_In raC_UDT_Itf_K5100_Cmd Tag Interface from device object.
Ref_Ctrl_Sts_In raC_UDT_Itf_K5100_Sts Tag Interface from device object.
Set_PositionReference LREAL
Immediate
value or
Tag
Set the Target Distance/Position Reference
(PUU)
Range: -2,147,483,648…+2,147,483,647
Set_SpeedReference LREAL
Immediate
value or
Tag
Units are 0.1 rpm for rotary motors.
Range: -80,000…+80,000
Set_AccelReference LREAL
Immediate
value or
Tag
Units are 0.1 rpm/s for rotary motors.
Range: 45830,000,000
Set_DecelReference LREAL
Immediate
value or
Tag
Units are 0.1 rpm/s for rotary motors.
Range: 45830,000,000
Set_MoveType INT
Immediate
value or
Tag
Specify the type of move:
0=Absolute
1=Incremental
2=Rotary Shortest Path
3=Rotary Positive
4=Rotary Negative
7=Relative
8=Capture
Set_PositionCommandOv
erride
BOOL
Immediate
value or
Tag
0 = Do not interrupt previous movement
1 = Interrupt previous movement
Set_PositionCommandOv
erlap
BOOL
Immediate
value or
Tag
0 = Current movement is not overlapped with
next
1 = Current movement is overlapped with next
movement
Set_CapturedPositionSele
ct
BOOL
Immediate
value or
Tag
0 = First High Speed Capture (triggered by
DI9)
1 = Second High Speed Capture (triggered by
DI10)
_ENO BOOL Tag True when this UDFB output is enabled.
Ref_Ctrl_Cfg_Out raC_UDT_Itf_K5100_Cfg Tag Interface to device object.
Ref_Ctrl_Set_Out raC_UDT_Itf_K5100_Set Tag Interface to device object.
Ref_Ctrl_Cmd_Out raC_UDT_Itf_K5100_Cmd Tag Interface to device object.
Ref_Ctrl_Sts_Out raC_UDT_Itf_K5100_Sts Tag Interface to device object.
Sts_EN (Enable) BOOL Tag
This bit is set when the rung makes a false-
to-true transition and remains set as the
message transaction to activate the drive is
initiated and in process. It remains set while
the rung-in condition is true and no faults are
active.
Sts_DN (Done) BOOL Tag
This bit is set when the rung makes a false-
to-true transition and the cmd to activate the
drive has been acknowledged.
Sts_ER (Error) BOOL Tag
This bit is set when the rung makes a false-
to-true transition and there is an error that
has occurred with the instruction. (This
instruction error can be a result of a fault on
the drive itself). See Sts_ERR for details on
the cause of the error.

Table of Contents

Other manuals for Rockwell Automation Allen-Bradley Micro830

Related product manuals