Publication 2711P-UM001D-EN-P - September 2005
6-4 Terminal Connections
Cables: PanelView Plus to Communication Adapters
1747-AIC
1761-NET-AIC
Protocol PanelView Plus Comm Port Port 1 (9-pin)
Port 2
8-pin Mini DIN()
Port 3
(DH485)
1761-NETDNI
or 1771-NET-ENI
DF1 (any) RS-232 Comm Port (9-pin)
PanelView Plus 400 -1500
2711P-RN22C
N/A
2711-NC13 (16ft/5m)
2711-NC14 (32ft/10m)
2706-NC13 (10ft/3m)
2711-NC21 (16ft/5m)
2711-NC22 (49ft/15m)
N/A
1761-CBL-AP00 (5m)
1761-CBL-PM02 (2m)
2711-CBL-PM05 (5m)
2711-CBL-PM10 (10m)
DH-485
(any)
RS-232 Comm Port (9-pin)
PanelView Plus 400 -1500
2711P-RN22C
N/A
2711-NC13 (16ft/5m)
2711-NC14 (32ft/10m)
2706-NC13 (10ft/3m)
2711-NC21 (16ft/5m)
2711-NC22 (49ft/15m) N/A
DH-485 Communication Port
PanelView Plus 400 -600
2711P-xxx3xx, 2711P-RN3
1747-C10 (6ft/2m)
1747-C11 (0.3m/1ft)
1747-C20 (20ft/6m)
N/A
1761-CBL-AS03
(10ft/3m)
1761-CBL-AS09
(30ft/9m)
to single AIC+
N/A
DH-485 Communication Port
PanelView Plus 700 -1500
2711P-xxx6xx, 2711P-RN6
Direct connection to
single AIC with
Belden 9842 cable
(1)
N/A
Direct connection to
single AIC+ with
Belden 9842 cable
(1)
N/A
(1)
Use serial port on terminal with an AIC+ module for a DH-485 network solution.