Publication 2711P-UM001D-EN-P - September 2005
3-6 Connect Power
Connect DC Power
1. Disconnect power to the terminal.
2. Secure the DC power wires to the terminal block screws.
Follow the markings on terminal blocks and terminal for proper
connections.
3. Secure the Functional Earth ground wire to the appropriate
terminal screw.
• On the 400 and 600 terminals, secure the Functional Earth
ground wire to the Functional Earth Ground terminal screw
on the input power terminal block.
• On the 700-1500 terminals, secure the Functional Earth
ground wire to the Functional Earth ground terminal screw at
the bottom of the display.
4. Apply 24V dc power to the terminal.
WARNING
Explosion Hazard - Do not connect or disconnect
equipment while circuit is live unless area is known
to be non-hazardous.
Disconnect all power before installing or replacing
components. Failure to disconnect power may result
in electrical shock and/or damage to the terminal.
+ DC Positive
- DC Negative
Functional Earth Ground
700 - 1500 Terminals
400 and 600 Terminals
- DC Negative
+ DC Positive
Functional Earth Ground
2-Position Terminal Block
Series E or later Logic Modules
3-Position Terminal Block
Series A-D Logic Modules
–
+
+
–