Specifications A-3
➀ For devices rated 5…480 A, heatsink fans can be powered by either 110/120V AC or 220/240V AC.
UL/CSA/NEMA IEC
Short Circuit Protection
SCPD Performance Type 1
SCPD List Max.
Available
Fault
Max.
Fuse
(A)
Max.
Available
Fault
Max.
Circuit
Breaker (A)
Line Device Operational Current
Rating (A)
5 10 kA 35 10 kA 35
25 10 kA 150 10 kA 150
43 10 kA 300 10 kA 300
60 10 kA 400 10 kA 300
85 10 kA 400 10 kA 400
108 30 kA 400 30 kA 300
135 30 kA 500 30 kA 400
201 30 kA 600 30 kA 600
251 30 kA 700 30 kA 700
317 42 kA 800 30 kA 800
361 42 kA 1000 30 kA 1000
480 42 kA 1200 30 kA 1200
Delta Device Operational Current
Rating (A)
8.7 10 kA 35 10 kA 35
43 10 kA 150 10 kA 150
74 10 kA 300 10 kA 300
104 10 kA 400 10 kA 300
147 10 kA 400 10 kA 400
187 30 kA 500 30 kA 500
234 30 kA 700 30 kA 700
348 30 kA 1000 30 kA 1000
435 42 kA 1200 30 kA 1200
549 42 kA 1600 30 kA 1600
625 42 kA 1600 30 kA 1600
831 42 kA 1600 30 kA 1600
Control Circuit
Rated Operational Voltage 100…240V AC
24V AC/24V DC
100…240V
24V ~/24V DC
Rated Insulation Voltage N/A 240V
Rated Impulse Voltage N/A 3000V
Dielectric Withstand 1600V AC 2000V
Operating Frequency 50/60 Hz 50/60 Hz
Protection Against Electric Shock N/A IP20
Power Requirements
Control Module 75 VA
Heatsink Fan(s) (A)
➀ 50 VA
Vibration
Operational 1 G
Non-Operational 2.5 G