4-14 Programming
All braking/stopping current settings in the range of 1…100% will provide 100% braking current
to the motor.
Option Parameter Range
Slow Speed
with Braking
SMC Option
This parameter identifies the type of
control present and is not user
programmable.
Braking Control
Slow Speed Select
Allows the user to program the slow
speed that best fits the application.
Low:7%
High:15%
Slow Accel Current
Allows the user to program the
required current to accelerate the
motor to slow speed operation.
0…450% of full load
current
Slow Running Current
Allows the user to program the
required current to operate the
motor at the slow speed setting.
0…450% of full load
current
Braking Current
Allows the user to program the
intensity of the braking current
applied to the motor.
0…400% of full load
current