Rockwell Automation Publication 520-UM001I-EN-E - July 2016 97
Programming and Parameters Chapter 3
Terminal Block Group (continued)
t089 [Analog Out High]
Scales the maximum output value (V or mA) when the source setting is at maximum.
(1)
Values Default: 100%
Min/Max: 0/800%
Display: 1%
(1) Parameter is also available in PowerFlex 523 FRN 3.xxx and later. PowerFlex 523 series B drive is required.
t090 [Anlg Out Setpt] Related Parameter(s): t088
Sets the percentage of output desired when t088 [Analog Out Sel] is set to 6, 14 or 22 “Analog Setpoint”.
(1)
Values Default: 0.0%
Min/Max: 0.0/100.0%
Display: 0.1%
(1) Parameter is also available in PowerFlex 523 FRN 3.xxx and later. PowerFlex 523 series B drive is required.
t091 [Anlg In 0-10V Lo] Related Parameter(s): P043, t092, t093
Stop drive before changing this parameter.
Sets the percentage (based on 10V) of input voltage applied to the 0-10V analog input used to represent P043 [Minimum Freq].
Analog inversion can be accomplished by setting this value larger than t092 [Anlg In 0-10V Hi].
If t093
[10V Bipolar Enbl] is set to 1 “Bi-Polar In”, this parameter is ignored.
Values Default: 0.0%
Min/Max: 0.0/200.0%
Display: 0.1%
t092 [Anlg In 0-10V Hi] Related Parameter(s): P044, t091, t093
Stop drive before changing this parameter.
Sets the percentage (based on 10V) of input voltage applied to the 0-10V analog input used to represent P044 [Maximum Freq].
Analog inversion can be accomplished by setting this value smaller than t091 [Anlg In 0-10V Lo].
If t093
[10V Bipolar Enbl] is set to 1 “Bi-Polar In”, the same value applies to positive and negative voltage.
Values Default: 100.0%
Min/Max: 0.0/200.0%
Display: 0.1%
t093 [10V Bipolar Enbl] Related Parameter(s): t091, t092
PowerFlex 525 only.
Enables/disables bi-polar control. In bi-polar mode direction is commanded by the polarity of the voltage.
If bi-polar control is enabled, P043
[Minimum Freq] and t091 [Anlg In 0-10V Lo] are ignored.
Options 0 “Uni-Polar In” (Default) 0-10V only
1 “Bi-Polar In ±10V
PF 525