7-6
SP500 AC Drive Installation and Operation Manual Version 3.1
A sample monitor mode display is shown in figure 7.4.
7.5.1 Displaying the Percent Selected Speed Reference
To display the percent selected speed reference, parameter F-13 must be set to ON.
Use the following procedure to display the percent selected speed reference:
Step 1. Stop the drive (if it is running) by pressing the STOP/RESET key.
Step 2. Enter program mode by pressing the MODE/ENTER key until the PROGRAM
LED turns on.
Step 3. Press the or key until F-13 is displayed.
Step 4. Press the MODE/ENTER key to access the parameter.
Step 5. Press the key until ON is displayed.
Step 6. Press the MODE/ENTER key to save the value. (F-13 will be displayed.)
Step 7. Press the STOP/REST key to exit program mode.
Step 8. Start the drive by pressing the START key.
Step 9. Press the MODE/ENTER key until all three monitor mode LEDs are on.
The display will show the active speed reference as 1 to 100% of maximum speed
(F-04).
7.5.2 Scaling the RPM Display and Reference Using F-08
The RPM display and reference can be scaled to an engineering unit to match your
application. Refer to the F-08 description in chapter 8 for this procedure.
7.6 Drive Control
When the control source is the local keypad (F-00 = 0), the keypad is used to control
the drive. This means that the drive will respond to START, STOP/RESET, and
FORWARD/REVERSE commands only from the keypad.
Figure 7.4 – Example of a Monitor Mode Display
Mode
Enter
START
Forward
Reverse
STOP
RESET
RPM
%Load
Volts
Remote
RUN
Program
Forward
Reverse