Programming Reference
8-17
This parameter is used with parameter F-26 (Auto-Restart Number of Attempts). Refer
to the F-26 parameter description for information regarding this feature.
Refer to table A.5 in Appendix A for more detail about the analog output.
F-27 Auto-Restart Retry Wait Time
This parameter
specifies the amount
of time the drive will
wait between auto-
restart attempts.
Parameter Range:
Default Setting:
Step Size:
1 to 30 seconds
1
1.0 second
F-28 Drive Voltage Selection
This parameter
displays the drive’s
voltage rating.
Parameter Range:
Default Setting:
Step Size:
N/A
N/A
N/A
!
ATTENTION:This parameter is set at the factory and must not be
changed by the user.
F-29 Analog Output Select
This parameter selects
which monitor mode
value is directed to the
analog output
(regardless of which
monitor mode value is
displayed).
Parameter Range:
Default Setting:
Step Size:
SPd = Current RPM/speed output
LOAd = Current percent load output
UOL = Current calculated output voltage
rEF = Current percent of selected reference
SPd
N/A
F-49 Version Information
This parameter
displays the software
version.
Parameter Range:
Default Setting:
Step Size:
N/A
N/A
N/A