9-8
SP500 AC Drive Installation and Operation Manual Version 3.1
.
* (+) DC bus volts power terminal
** (–) DC bus volts power terminal
* (+) DC bus volts power terminal
** (–) DC bus volts power terminal
Table 9.2 – Resistance Checks for Input Diodes
Input
Diode
No.
Meter
Connection
Component is OK if
resistance (R) is:
Component is
defective if:(+) (-)
1 * R/L1 50 < R < 10 Megohm Continuity (short circuit) or
open when the meter is
connected with reversed
polarity.
2*S/L2
3*T/L3
4R/L1 **
5S/L2 **
6T/L3 **
Table 9.3 – Resistance Checks for IGBTs
IGBT
No.
Meter
Connection
Component is OK if
resistance (R) is:
Component is
defective if:(+) (–)
1 * W/T3 50 < R < 10 Megohm Continuity (short circuit) or
open when the meter is
connected with reversed
polarity.
2*V/T2
3*U/T1
4W/T3 **
5V/T2 **
6U/T1 **