EasyManua.ls Logo

Rosemount 333 HART Tri-Loop - Troubleshooting HART Tri-Loop Issues; Tri-Loop Troubleshooting Table

Rosemount 333 HART Tri-Loop
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section
4-1
4 Troubleshooting
Table 4-1 provides troubleshooting suggestions for the most common
operating problems.
TABLE 4-1. Tri-Loop Troubleshooting
Table.
Symptom Corrective Action
No Communication
between the HART
Tri-Loop Configurator
Software and the Tri-Loop
LOOP WIRING
Close both EA software and Tri-Loop Configurator software,
then restart the Tri-Loop Configurator software.
HART protocol communication requires a loop resistance
value between 250–1100 ohms, inclusive.
Checkfor adequate voltage to the Tri-Loop.(Channel 1 must be
powered for the Tri-Loop to operate.)
Check for intermittent shorts, open circuits, and multiple
grounds.
Check for capacitance across the load resistor. Capacitance
should be less than 0.1 microfarad.
TRI-LOOP SOFTWARE INSTALLATION
Verify computer reboot followed software installation.
Verify correct COMM port selected.
Verify laptop computer is not in low energy mode
(certain laptops disable all COMM ports in low energy mode).
Did you install software onto Windows NT platform?
(Configurator software will only work with Windows 3.1,
Windows for Workgroups 3.11, or Windows 95.)
Check if HART driver was subsequently over-written during a
Model 3095 MV Engineering Assistant installation. If this has
occurred, reinstall the Configurator software.
Check the DEVICEHIGH statement in the CONFIG.SYS
statement as explained in the Configurator “readme” file.
Burst Commands not
received from Model 3095
MV
Verify the Model 3095 MV is set to Burst Command 3.
Checkfor adequate voltage to the Tri-Loop.(Channel 1 must be
powered for the Tri-Loop to operate.)
Check for intermittent shorts, open circuits, and multiple
grounds.
HART protocol communication requires a loop resistance
value between 250–1100 ohms, inclusive. Typically, the
required resistance is installed during the Model 3095 MV
installation.
Tri-Loop Channel is in
Alarm
Use the HART Tri-Loop Configurator, and select
D
iagnostics, Error Info to determine the cause of the alarm.
For information on any error message, use the Configurator
on-line help files.
Channel 1 operates
correctly, but Channel 2
(or Channel 3) does not
Check for proper loop resistance for the channel. Each
channel must have it’s own power supply and required loop
resistance (see page 2-5).
Win32S error
Runtime Error!
If you receive a Win32s or Runtime error, remove Win32s and
reinstall the Configurator software as explained in the
Configurator “readme” file.

Table of Contents