EasyManua.ls Logo

Rosemount 333 HART Tri-Loop - Configuration Procedure

Rosemount 333 HART Tri-Loop
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HART Tri-Loop HART-to-Analog Signal Converter
3-4
Configuration Procedure
The following procedure outlines the major steps needed to configure a
Tri-Loop. For more detailed information, use the Configurator on-line
help screens.
1. Double click on the HART Tri-Loop Configurator Software icon.
2. Select T
ri-Loop, Connect to Tri-Loop to display the connect
screen, then connect to a Tri-Loop.
NOTE
If you are unable to connect to a Tri-Loop, see Table 4-1 on page 4-1 for
suggestions.
3. Select C
onfiguration, Configure Channels to display the HART
Tri-Loop Configuration Screen (Figure 3-3).
a. Click Channel 1, and select the process variable for this
channel, desired range, and
exact
Model 3095 MV units.
If required, click on the Enabled box so that the Tri-Loop
analog output will be enabled.
b. (Optional) Repeat step a for Channels 2 and 3.
c. Click device information, enter the desired tag, descriptor, and
message information, then select OK.
4. Select C
onfiguration, Save to Tri-Loop to send the configuration
to a Tri-Loop.
5. Select C
onfiguration, Open from Tri-loop to verify that the
configuration was correctly received. The Tri-Loop configuration
information will be displayed in the main window of the HART
Tri-Loop Configurator software.
6. If necessary, perform an analog output trim (T
ri-Loop, Trim
Outputs) for each enabled Tri-Loop analog output.
7. Complete the connection between the Model 3095 MV analog
output and the Tri-Loop Burst Input as illustrated in Figure 3-4.
8. Use a multimeter or the control room equipment to verify that
each new Tri-Loop channel is transmitting the Model 3095 MV
process variables.
FIGURE 3-3. HART Tri-Loop
Configuration Screen.
3095-30950702

Table of Contents