ROXELL - 025 - 2416
SPARKcup- USER'S GUIDE -EUG
10
MANUAL FLUSHING (STANDARD)
Flushing button on pressure
regulator
Figure 1.
Each Sparkcup drinking line has a standard manual flushing system. This allows flushing the water pipes at random.
Procedure :
1. Open the end ball valve.
2. Turn the flushing button in high position (complete ”flush”).
3. The water is sent through the lines under full incoming pressure.
Ideal flushing : an incoming pressure of 3 bar and a
capacity of about 10 liters
per minute per line. Flush during 1 minute per 10 m line length.
4. Set back the flushing button in the normal position.
5. Shut off the end ball valve.
RESPECT THE PROCEDURE BELOW :
IF NOT, THE TOTAL SYSTEM IS UNNECESSARILY PUT UNDER
TOO HIGH PRESSURE WITH DAMAGE RISK !
Turn into flushing position
End ball valve
All lines can be flushed simultaneously when following the specifications for the right water supply.
With a low pressure water supply it is better to flush half of the lines or even line per line.
CAUTION