EasyManuals Logo

Russelectric RTS03 Series User Manual

Russelectric RTS03 Series
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
O&M Manual –90E1720004
Section 7 Energizing the Bypass-Isolation Transfer Switch Page 26 of 52
l. Verify that the transfer switch transfers to the S2 source by check the
status on the RPTCS OIP.
m. Cancel the load test and verify that the engine shuts down.
n. Take the bypass switch out of bypass to the non-bypass position.
o. Close all downstream load circuit breakers.
p. Perform a load test.
q. Verify that the transfer switch transfers to the S2 source by checking the
status on the RPTCS OIP.
r. Cancel the load test and verify that the engine shuts down.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Russelectric RTS03 Series and is the answer not in the manual?

Russelectric RTS03 Series Specifications

General IconGeneral
BrandRusselectric
ModelRTS03 Series
CategorySwitch
LanguageEnglish

Related product manuals