72 VG5 Installation & Quick-Start Manual
Monitor
U1-12
Operation Status*
(Int Ctl Sts 1)
Q Q Q Q
U1-13
Elapsed Time*
(Elapsed Time)
1 hour Q Q Q Q
U1-14
Software No. at FLASH
Side*
(FLASH ID)
Q Q Q Q
U1-15
Control Circuit
Terminal 13
(Term 13 Level)
0.1% 10V/10V B B B B
U1-16
Control Circuit Terminal
14 Input Voltage (Term 14
Level)
0.1% —
10V/10V or
20 mA
B B B B
U1-17
Control Circuit Terminal
16 Input
(Terminal 16 Level)
0.1% 10V/10V B B B B
U1-18
Motor Secondary
Current (Iq)
(Mot SEC Current)
0.1% —
10V/Motor
rated
primary
current
B B B B
U1-19
Motor Excitation
Current (Mot EXC Cur-
rent)
0.1% —
10V/Motor
rated
primary
current
x x B B
U1-20
Output Frequency after
Soft-start
(SFS Output)
0.01Hz —
10V/Max.
output
frequency
A A A A
U1-21
ASR Input
(ASR Input)
0.01% —
10V/Max.
output
frequency
x A x A
U1-22
ASR Output
(ASR Output)
0.01%
Analog monitor output level becomes 10V/Max. out-
put frequency for V/f control mode with PG.
10V/Motor
rated
primary
current
x A x A
U1-23
Speed Deviation
(Speed Deviation)
0.01% —
10V/Max.
output
Frequency
x A x A
U1-24
PID Feedback Capacity
(PID Feedback)
0.01% –
10V/Max.
output
Frequency
A A A A
Function
Parameter
No.
Name
(Digital Operator Display)
Min.
Unit
Description
Analog
Monitor
Output Level
Parameter Access Level
V/f
V/f w/
PG
Vector
w/o
PG
Vector
w/ PG
1: During running
1: During zero speed
1: During reverse
1: During reset signal input
1: During speed agree
1: Inverter operation ready
1: Minor fault
1: Major fault
0 0 0 0 0 0 0 0
Appendix
VG5 Parameter List U Monitor
* Cannot be changed by U1-04