VG5 Installation & Quick-Start Manual 93
Group F Options *
Function F1 PG Option Setup
F1-09
Overspeed
Detection Delay
Time
(PG Overspd Time)
0.0~2.0 0.1s 0.0*
* When A1-02=1 [V/f w/PG] fac-
tory setting is 1.0. When A1-
02=3 [ Flux Vector] factory set-
ting is 0.0.
x - A - A
F1-10
Excessive Speed
Deviation Detection
Level
(PG Deviate Level)
0~50 1% 10 x - A - A
F1-11
Excessive Speed
Deviation detection
Delay Time
(PG Deviate Time)
0.0~
10.0
0.1s 0.5 x - A - A
F1-12
Number of PG Gear
Teeth 1
(PG # Gear Teeth
1)
0~1000 1 0 x - A - -
F1-13
Number of PG Gear
Teeth 2
(PG # Gear Teeth
2)
0~1000 1 0 x - A - -
F1-14
PGO Detection
Time
(PGO Detect Time)
0~10.0 0.1s 2.0 x - A - A
Function F2 AI-14 Setup
F2-01
AI-14B Card Input
Selection
(AI-14 Input Sel)
0, 1 1 0
0: (3-ch Individual)
1: (3ch Addition)
x A A A A
* When access level is BASIC (A1-03), constant is not displayed unless the option is connected.
Function
Parameter
No.
Name
(Digital Operator
Display)
Setting
Range
Setting
Unit
Factory
Setting
Remarks
(Digital Operator Display)
Change
during
Operation
o: Enabled
x: Disabled
Parameter Access Level
User
Setting
V/f
V/f
w/
PG
Open
Loop
Vector
Flux
Vector
Appendix
VG5 Parameters