8000m Series
- 102 -
F8.04
Deceleration time 2 Factory Setting
Defined by
inverter model
Setting Options 0.1~3600s
F8.05
Acceleration time 3 Factory Setting
Defined by
inverter model
Setting Options 0.1~3600s
F8.06
Deceleration time 3 Factory Setting
Defined by
inverter model
Setting Options 0.1~3600s
F8.07
Acceleration time 4 Factory Setting
Defined by
inverter model
Setting Options 0.1~3600s
F8.08
Deceleration time 4 Factory Setting
Defined by
inverter model
Setting Options 0.1~3600s
For the VFD acceleration and deceleration time, there are F0.18 and F0.19 and the
above-mentioned three pairs of acceleration and deceleration time, all these have
the same definition. Please refer to the descriptions of parameter F0.18 and F0.19.
During the operation of AC drive, acceleration/deceleration time1~4 can be chosen
through combinations of multi-function digital input terminals. For more details,
see the descriptions of function code 21 and 22 for parameter F5.01 to F5.05.
F8.09
Jump frequency 1 Factory Setting 0.00Hz
Setting Options 0.00~F0.10
F8.10
Jump frequency 2 Factory Setting 0.00Hz
Setting Options 0.00~F0.10
F8.11
Jump frequency width Factory Setting 0.00Hz
Setting Options 0.00~F0.10
If the frequency reference is within the frequency jump range, the actual running