8000m Series
- 107 -
Setting Options 0.00~Maxi. frequency
F8.23
Upper limit of
frequency detecting
Factory Setting 40.00Hz
Setting Options 0.00~Maxi. frequency
When the multi-function digit output terminals are defined as “Running frequency
detection”, these two parameters are used to define the upper and lower limits for
the frequency detecting. If the running frequency is less or equal to F8.22(Lower
limit of frequency detecting), or is greater or equal to F8.23(Upper limit of
frequency detecting), the corresponding multi-function digit output terminal will
be “ON”; If the running frequency is between F8.22 and F8.23, the terminal will
be “OFF”.
F8.24 Reserved
F8.25
Inverter rated power Factory Setting
Defined by
inverter model
Setting Options 0.4~700.0kW
F8.26
Inverter rated current Factory Setting
Defined by
inverter model
Setting Options 0.0~2000A
These parameters are for the reference of the rated power and rated current, not for
modification.
F8.27
Linear speed display
coefficient
Factory Setting 1.00%
Setting Options
0.1~ 999.9% (linear speed = mechanical
speed * F8.27)
Linear speed = mechanical revolution * F8.27. This parameter is for the calibration
of linear speed display.