8000m Series
- 112 -
F9.07
Sampling period (T) Factory Setting 0.10s
Setting Options 0.01~100.0s
F9.08
PID control deviation limit Factory Setting 0.00%
Setting Options 0.0~100.0%
Sampling period(T): It refers to the sampling period of feedback signal, and the
PID control calculates once a sampling period. The longer the sampling period is,
the slower the response time.
PID control deviation limit: The limit of PID feedback deviation to PID setting
value, which is for the PID control output as in following illustration. Between the
upper and lower PID control deviation limit, PID control will stop regulating.
Make proper setting of this parameter will result in accuracy, stability of PID
control response.
F9.09
Feedback loss detecting value Factory Setting 0.00%
Setting Options 0.0~100.0%
F9.10
Feedback loss detecting time Factory Setting 1.0s
Setting Options 0.0~3600.0s