8000m Series
- 114 -
than PID wake-up threshold, VFD will start PID wake-up detecting. After PID
wake-up detecting delay time, if the feedback is still lower than wake-up threshold,
wake-up will be success and VFD returns to PID control mode, or it is fail for
wake-up. If the setting of PID wake-up threshold is too high it will result in VFD
restarting frequently, or if it is too low it will result in too low pressure of output.
F9.16
PID Lower retaining
frequency running time
Factory Setting 10.0s
Setting Options 0.0~3600.0s
F9.17~F9.18 Reserved