EasyManuals Logo

SAJ 8000m Series User Manual

SAJ 8000m Series
153 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #120 background imageLoading...
Page #120 background image
8000m Series
- 119 -
FA.08
Auto current limiting
selection
Factory Setting 0
Setting Options
0 Enabled
1 Disabled at constant speed
FA.09
Fault auto-reset times Factory Setting 0
Setting Options 0~3
This parameter is for setting auto reset times of fault when VFD is chosen to
automatically reset fault. If the times of resetting is over than this value, the VFD
will stop and waiting for maintenance.
FA.10
Fault auto-reset interval Factory Setting 1.0s
Setting Options 0.1~100.0s
This parameter defines the waiting time from VFD fault trigging to fault auto
resetting.
FA.11 Reserved
FA.13
Phase-lack protection of output Factory Setting 1
Setting Options
0 Disabled
1 Enabled
FA.13 is for choosing protection of output phase-lack fault or not.
FA.14 Faults type last two time
0~26
FA.15 Fault Type last time
FA.16 Current fault type
These parameters record the recent 3 fault types: 0 is no fault, 1~26 are
E001~E026 (FULL). For the details please refer to Trouble Shooting.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SAJ 8000m Series and is the answer not in the manual?

SAJ 8000m Series Specifications

General IconGeneral
BrandSAJ
Model8000m Series
CategoryController
LanguageEnglish

Related product manuals