8000m Series
- 53 -
Function
Code
Function Descriptions
Minimum
Unit
Factory
Setting
Modifica-
tion Type
FC.04
Communication
timeout fault
setting
0.0 (invalid), 0.1~100.0s 0.1s 0.0s ○
FC.05
Method of
disposing
communication
timeout fault
0:Alarm and coast to stop
1:No alarm and continue to run
2:No alarm but stop according
to
F1.05 (only when F0.01= 2)
3: No alarm but stop according
to F1.05
1 ○
FC.06
Transmission
response action
Unit’s digit:
0: Response to writing
1: No response to writing
Ten’s place:
0:Value not saved when
poweroff
1: Value saved when power-off
0 ○
FD Group:Multi-step Speed and Simple PLC Parameters
FD.00
Simple PLC
operation method
0:Stop after operation once time
1:Keep the f inal value af ter
operation once time 2:Operation
in cycles
0 ○
FD.01
Memory option of
simple PLC when
power-off
0: Invalid 1:Valid 0 ○
FD.02 Multi-step speed 0 -100~100% 0.10% 0.00% ○
FD.03
0
th
step running
time
0.0~6553s(m) 0.1s(m) 0.0s ○
FD.04 Multi-step speed 1 -100~100% 0.10% 0.00% ○
FD.05
1
st
step running
time
0.0~6553s(m) 0.1s(m) 0.0s ○