8000m Series
- 75 -
Under speed control mode, the VFD output the maximum value of torque, set
100.0% which is correspondent to the rated output(or rated torque) current of the
VFD.
0:no detection
1: Overload pre-alarm is detected effective in operation (including acceleration,
deceleration and constant speed), go on operation after detection
2: Overload pre-alarm is detected effective in operation (including acceleration,
give alarm (E023) and stop after detection
3: Overload pre-alarm is detected effective in constant speed, go on operation after
detection
4: Overload pre-alarm is detected effective in constant speed, go on operation after
detection, give alarm (E023)and stop after detection
F3.07
Upper limit torque Factory Setting 150%
Setting Options
0.0 ~200.0% (Drive rated current)
F3.08-F3.09 Reserved
F3.10
Pre-alarm option when overload Factory Setting 1
Setting Options
0 ~4
F3.11
Detecting level of pre-alarm when
overload
Factory Setting 150.00%
Setting Options
1.0~200.0% (referred to inverter
rated current)
F3.12
Detecting time of pre-alarm when
overload
Factory Setting 1s
Setting Options 0~600s