128
Fig. FA-3 Off Load Detection
Notice
With the setting of parameter FA.12 and
FA.13, when the output current of the
driver is higher than overload pre-alarm
level (FA.12), the driver will send pre-alarm
signal after delay time (FA.13), i.e. the
control panel will display "A-09".
Overload pre-alarm function is mainly used
for monitoring overload condition before
overload protection action. Overload pre-
alarm level defines the current threshold of
FA.12
Overload pre-alarm level
G tyep: 20%~ 200% *VFD
rated current 160%
P tyep: 20%~ 200% *VFD
rated current 120%
Depending
on model
This parameter defines the delay time from
the time when the output current of VFD is
higher than the overload pre-alarm level
(FA.12) to the time when overload pre-alarm
signal is sent.
FA.13
Overload pre-alarm delay
0.0 300s 10.0
For details see function description NO.51 of
F7.18 F7.21.
FA.14
Temperature detection threshold
0.0℃~ 90.0℃ 65.0℃
0: both invalid
1: invalid for input, valid for output
2: valid for input, invalid for output
3: both valid
Factory default I for VFD under 7.5kW,
factory default 3 for VFD above 11kW.
FA.15
Phase loss protection of input/output
0~3
Depending
on model
7BMJE
5JNF
0GG-PBE
%FUFDUJPO5JNF
0GG-PBE
%FUFDUJPO5JNF
0VUQVU
$VSSFOU
0GG-PBE
%FUFDUJPO
-FWFM
0GG-PBE
%FUFDUJPO
"DUJPO
4.2 Detailed Function Description
0: o󽗈 load detection disabled
O󽗈 load detection level (FA.10) de󽗉nes the
current threshold of o󽗈 load action, and the
set value is the percentage relative to rated
current of the VFD.
O󽗈 load time (FA.10) de󽗉nes the lasting time
that the driver output current is lower than
o󽗈 load detection level (FA.11) continuously,
after which the o󽗈 load signal is sent.
Off load status valid means that the
operating current of the driver is lower than
o󽗈 load detection level and the lasting time
exceeds o󽗈 load detection time.
FA.10
O󽗈 load detection time
0.1S 60.0S 5.0
FA.11
O󽗈 load detection level
0.0 100.0%*rated
current of VFD
0.0%
overload pre-alarm action, and the set value is
the percentage relative to the rated current of
VFD.