Appendix 2: 600 Series Guide for Rapid Debugging of Constant-pressure Water Supply
3
4
5
'8%
6
7
8
(/%
7
"*
"$_
,
$0.
3FNPUFQSFTTVSFHBVHF
.
3FEXJSF
(SFFOXJSF
:FMMPXXJSF
F0.05=0 V/F control
F0.06=1 terminal run command
F0.07=8 PID control
F8.01=5 pressure setting(MPa、Kg)
F8.06=0.5 integral time
F8.13=1 coast to stop in sleep mode
F8.15=100 sleep threshold value
F8.16=90 awake threshold value
F8.17=1.0 sleep delay time
F8.18=1.0 awake delay time
F8.25=10.00 sensor range is 1MPa(10Kg)
F8.26=5.00 set pressure as 5Kg
F8.34=30.0 sleep frequency