5.9 Communication Address of all Parameters:
Notice:
In the above examples, the driver address is 01, which makes it better for illustration; when
the driver is slave, the address setting range is 1 247, and if any data of frame format is
changed, the check code needs to be recalculated. The calculating tools of 16bit CRC check
code can be download from internet.
Initial address of monitor item is D000, each item offset corresponding hexadecimal value
based on this address, then plus it with the initial address. For example: the monitor initial
item is d-00, the corresponding initial address is D000H (1D00H), now read monitor item
d-18, 18-00=18, the corresponding hexadecimal of 18 is 12H, then the read address of d-18 is
D000H+12H = D012H (1D00H+12H = 1D12H). Address D000H and 1D00H are interchangeable.
Frame format when the slave response information is abnormal: driver address +
(80H+function code) + 16bit CRC check code; if the salve return frame is 01H + 83H + 04H +
40F3H, then 01H is slave address, 83H is 80H+03H indicating read error, 04H is invalid data
length, 40F3H is 16bit CRC check code.
Function code Communication address
F0.00 F0.22 0000H 0016H
F1.00 F1.37 0100H 0125H
F2.00 F2.17 0200H 0211H
F3.00 F3.08 0300H 0308H
F4.00 F4.27 0400H 041BH
F5.00 F5.24 0500H 0518H
F6.00 F6.52 0600H 0634H
F7.00 F7.36 0700H 0724H
F8.00 F8.33 0800H 0821H
F9.00 F9.73 0900H 0949H
FA.00 FA.35 0A00H 0A23H
FB.00 FB.07 0B00H 0B07H
FC.00 FC.28 0C00H 0C1CH
FE.00 FE.15 0E00H 0E0FH
FF.00 FF.22 0F00H 0F16H
d-00 d-57 D000H(1D00H)~ D039H(1D39H)