EasyManua.ls Logo

Sako SKI600 - Function Code; F0 Group - Basic Run Parameters

Sako SKI600
180 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
029
4.1 Function Code
○—modi󽗉able parameter under any candition ×—nat modi󽗉able parameter under run status
◆—the actual detected parameter, not modi󽗉able ◇—factory parameter, only modi󽗉able for
factory, not allowed for users modifying
F0 Group - Basic Run Parameters
Function
Code
Name Set Range
Minimum
Unit
Factory
Default
Modi󽗉cation
F0.00 / / / / ×
F0.01
Control software
version
1.00 99.99 0.01 1.02
F0.02
Operation panel
software version
1.00 99.99 0.01 1.00
F0.03 VFD rated power 0.4 999.9KW(G/P) 0.1KW
Depending
on model
F0.04 VFD type
0: G type ( constant torque load
type)
1: P type (fan, water pump load
type)
Note 1: set as P type, and the VFD
parameters will refresh
automatically, without modifying
any parameter the VFD can be
used as inverter of higher grade for
application of fan and water
pump.
Note 2: can not be initialized,
please modify it manually.
1 0 ×