029
4.1 Function Code
○—modiable parameter under any candition ×—nat modiable parameter under run status
◆—the actual detected parameter, not modiable ◇—factory parameter, only modiable for
factory, not allowed for users modifying
F0 Group - Basic Run Parameters
Function
Code
Name Set Range
Minimum
Unit
Factory
Default
Modication
F0.00 / / / / ×
F0.01
Control software
version
1.00 ~ 99.99 0.01 1.02 ◆
F0.02
Operation panel
software version
1.00 ~ 99.99 0.01 1.00 ◆
F0.03 VFD rated power 0.4 ~ 999.9KW(G/P) 0.1KW
Depending
on model
◆
F0.04 VFD type
0: G type ( constant torque load
type)
1: P type (fan, water pump load
type)
Note 1: set as P type, and the VFD
parameters will refresh
automatically, without modifying
any parameter the VFD can be
used as inverter of higher grade for
application of fan and water
pump.
Note 2: can not be initialized,
please modify it manually.
1 0 ×