60 | SAMLEX AMERICA INC.
SECTION 3 | Installation
b) AC Output Grounding: The metal chassis of the AC load(s) get connected to the Grounding Electrode (GE) /
Ground Rod of the premises as follows:
• The metal chassis of the AC load(s) is connected to the Grounding socket (G) of the GFCI outlet (10) in EVO™
through the Grounding Conductor of the load connection
• Grounding socket (G) of GFCI outlet “10” in EVO™ is connected to the metal chassis of EVO™.
• The metal chassis of EVO™ is connected to the Grounding Pin (G) of the AC Power Inlet Plug (9)
• The grounding Pin (G) of the AC Power Inlet (9) gets connected to the Grounding Bus Bar (G-B) in the Grid
Electrical Panel through the grounding wire of AC input connection
• The Grounding Bus Bar (G-B) in the Grid Electrical Panel is bonded to Earth Ground through the Grounding
Electrode (GE) / “Ground Rod” of the premises
3.14.2.2 EVO-1212F-HW and EVO-1224F-HW: AC Side Grounding of Typical Shore Based Installation
Refer to the Installation Diagram for Typical Shore Based Installation for EVO-1212F-HW and EVO-1224F-HW at Fig 3.13
a) AC Input Grounding: The metal chassis of EVO™ gets bonded to the Grounding Electrode (GE) / “Ground Rod”
of the premises as follows:
• The metal chassis of EVO™ is connected to the “INPUT GND” Terminal (23) of the AC Input / Output Terminal
Block (20) in EVO™
• The “INPUT GND” Terminal (23) of the AC Input / Output Terminal Block (20) in EVO™ gets connected to the
Grounding Bus Bar (G-B) in the Grid Electrical Panel through the grounding wire of AC input connection
• The Grounding Bus Bar (G-B) in the Grid Electrical Panel is bonded to Earth Ground through the Grounding
Electrode (GE) / “Ground Rod” of the premises
b) AC Output Grounding: The metal chassis of the AC load(s) gets connected to the Grounding Electrode (GE) /
“Ground Rod” of the premises as follows:
• The metal chassis of the AC load(s) is connected to the Grounding Bus Bar (G-B) of the Electrical Sub Panel for
EVO™ Output
• Grounding Bus Bar (G-B) of the Electrical Sub Panel for EVO™ Output is connected to metal chassis of EVO™
through the “OUTPUT GND” Terminal (26) of the AC Input / Output Terminal Block (20) in EVO™.
• The metal chassis of EVO™ is connected to the “INPUT GND” Terminal (23) of the AC Input / Output Terminal
Block (20) in EVO™
• The “INPUT GND” Terminal (23) of the AC Input / Output Terminal Block (20) in EVO™ gets connected to the
Grounding Bus Bar (G-B) in the Grid Electrical Panel through the grounding wire of AC input connection
• The Grounding Bus Bar (G-B) in the Grid Electrical Panel is bonded to Earth Ground through the Grounding
Electrode (GE) / “Ground Rod” of the premises
3.14.3 AC Side Grounding of Typical RV / Mobile Installation
3.14.3.1 EVO-1212F and EVO-1224F: AC Side Grounding of Typical RV / Mobile Installation
Refer to the Installation Diagram for Typical RV / Mobile Installation for EVO-1212F and EVO-1224F at Fig 3.14.