60 | SAMLEX AMERICA INC.
SECTION 3 | Installation
b) AC Output Grounding: The metal chassis of the AC load(s) get connected to the Grounding Electrode (GE) /
Ground Rod of the premises as follows:
The metal chassis of the AC load(s) is connected to the Grounding socket (G) of the GFCI outlet (10) in EVO™
through the Grounding Conductor of the load connection
Grounding socket (G) of GFCI outlet “10” in EVO™ is connected to the metal chassis of EVO™.
The metal chassis of EVO™ is connected to the Grounding Pin (G) of the AC Power Inlet Plug (9)
The grounding Pin (G) of the AC Power Inlet (9) gets connected to the Grounding Bus Bar (G-B) in the Grid
Electrical Panel through the grounding wire of AC input connection
The Grounding Bus Bar (G-B) in the Grid Electrical Panel is bonded to Earth Ground through the Grounding
Electrode (GE) / “Ground Rod” of the premises
3.14.2.2 EVO-1212F-HW and EVO-1224F-HW: AC Side Grounding of Typical Shore Based Installation
Refer to the Installation Diagram for Typical Shore Based Installation for EVO-1212F-HW and EVO-1224F-HW at Fig 3.13
a) AC Input Grounding: The metal chassis of EVO™ gets bonded to the Grounding Electrode (GE) / “Ground Rod”
of the premises as follows:
The metal chassis of EVO™ is connected to the “INPUT GND” Terminal (23) of the AC Input / Output Terminal
Block (20) in EVO™
The “INPUT GND” Terminal (23) of the AC Input / Output Terminal Block (20) in EVO™ gets connected to the
Grounding Bus Bar (G-B) in the Grid Electrical Panel through the grounding wire of AC input connection
The Grounding Bus Bar (G-B) in the Grid Electrical Panel is bonded to Earth Ground through the Grounding
Electrode (GE) / “Ground Rod” of the premises
b) AC Output Grounding: The metal chassis of the AC load(s) gets connected to the Grounding Electrode (GE) /
“Ground Rod” of the premises as follows:
The metal chassis of the AC load(s) is connected to the Grounding Bus Bar (G-B) of the Electrical Sub Panel for
EVO™ Output
Grounding Bus Bar (G-B) of the Electrical Sub Panel for EVO™ Output is connected to metal chassis of EVO™
through the “OUTPUT GND” Terminal (26) of the AC Input / Output Terminal Block (20) in EVO™.
The metal chassis of EVO™ is connected to the “INPUT GND” Terminal (23) of the AC Input / Output Terminal
Block (20) in EVO™
The “INPUT GND” Terminal (23) of the AC Input / Output Terminal Block (20) in EVO™ gets connected to the
Grounding Bus Bar (G-B) in the Grid Electrical Panel through the grounding wire of AC input connection
The Grounding Bus Bar (G-B) in the Grid Electrical Panel is bonded to Earth Ground through the Grounding
Electrode (GE) / “Ground Rod” of the premises
3.14.3 AC Side Grounding of Typical RV / Mobile Installation
3.14.3.1 EVO-1212F and EVO-1224F: AC Side Grounding of Typical RV / Mobile Installation
Refer to the Installation Diagram for Typical RV / Mobile Installation for EVO-1212F and EVO-1224F at Fig 3.14.