EasyManua.ls Logo

Samson 3730-2 - MAX - Initialization Based on Maximum Range

Samson 3730-2
176 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
102 EB 8384-2 EN
Operating the positioner
Fail-safe position AIR TO CLOSE
IftheslideswitchissettoAIRTOCLOSE,
the positioner automatically switches to the
directionofactionincreasing/decreasing
(äæ) after initialization has been complet-
ed. This results in the assignment (left) be-
tween set point and valve position.
The tight-closing function has been activat-
ed.
Set Code 15 (set point cutoff increase) to
99% for three-way valves.
Fail-safe
position
Direction of
action
Set point
Valve
CLOSED
at
OPEN at
Actuator stem
extends (FA)
AIRTOOPEN

0% 100%
Actuator stem
retracts (FE)
AIRTOCLOSE

100% 0%
7.6.1 MAX – Initialization based on maximum range
Thepositionerdeterminestravel/angleofrotationoftheclosingmemberfromtheCLOSED
positiontotheoppositetravelstopandadoptsthistravel/angleofrotationastheoperating
rangefrom0to100%.
Enable conguration:
Ifnosettingsareenteredwithin120seconds,theenabledcongurationfunctionbecomesin-
valid.
1. Turn untilCode3appears(reading:
No).
2. Press , the code number 3 blinks.
3. Turn
until YES appears.
4. Press
toconrm(reading: ).
Enableconguration
Default: No
Select the initialization mode:
1. Turn untilCode6appears.
2. Press
, the code number 6 blinks.
3. Turn
until MAX appears.
4. Press
toconrmtheMAXinitialization
mode.
Default: MAX

Table of Contents

Other manuals for Samson 3730-2

Related product manuals