104 EB 8384-2 EN
Operating the positioner
Enable conguration:
Ifnosettingsareenteredwithin120seconds,theenabledcongurationfunctionbecomesin-
valid.
1. Turn untilCode3appears(reading:
No).
2. Press , the code number 3 blinks.
3. Turn
until YES appears.
4. Press
toconrm(reading: ).
Enableconguration
Default: No
Enter the pin position and nominal range:
1. Turn untilCode4appears.
2. Press
, the code number 4 blinks.
3. Turn
to select pin position on lever (see
relevant section on attachment).
4. Press toconrm.
5. Turn
untilCode5appears.
6. Press
, the code number 5 blinks.
7. Turn
and set nominal travel of the valve.
8. Press
toconrm.
mm
Pin position
Default: No
mm
Nominal range
(lockedwhenCode4=
No)
Select the initialization mode:
1. Turn untilCode6appears.
2. Press
, the code number 6 blinks.
3. Turn
until NOM appears.
4. Press
toconrmtheNOMinitialization
mode.
Init mode
Default: MAX