134 EB 8384-2 EN
Appendix
Code
no.
Parameter–Readings/
values [default setting]
Description
36* Reset
[No], Std, diAG, ESC
Std: Resetsallparametersanddiagnosisdatatotheirdefault
settings. After a reset, the positioner must be re-initialized.
diAG: Resetsdiagnosisdataonly.Plottedreferencegraphsand
logs remain saved.
The positioner does not need to be re-initialized.
37* Position transmitter
No, YES
Readonly
Indicates whether an optional position transmitter is installed.
38* Inductive alarm
[No], YES, ESC
Indicates whether the inductive limit switch option is installed or not.
39 Set point deviation e info
–99.9to99.9%
Readonly
Indicatesthedeviationfromthetargetposition(e=w–x).
40 Transit time Open info
[0]to240s
Readonly
Minimum opening time determined during initialization.
41 Transit time Closed info
[0]to240s
Readonly
Minimum closing time determined during initialization.
42 Auto-w info
0.0to100.0%ofthe
span
Readonly
Indicates the applied automatic set point with corresponding 4 to
20mAsignal.
43 Firmware info Readonly
Indicatesthepositionertypeandcurrentrmwareversionin
alternating sequence.
44 y info
[0]to100%,0P,MAX,
–––
Readonly
Indicatesthecontrolsignalyin%inrelationtothetravelrange
determined during initialization.
MAX: The positioner builds up its maximum output pressure,
seedescriptioninCode14and15.
0P: The positioner vents completely, see description in
Code14and15.
–––: The positioner is not initialized.