Turn until the OPEN position of the valve
is reached.
Press to confirm the OPEN position.
Enable configuration:
Note: If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
Configuration enabled
Default: No
Turn
Code 3, display: No
Press , Code 3 blinks.
Turn
YES
Press , display:
Enter pin position:
Pin position
Default: No
Turn
Code 4
Press , Code
4 blinks.
Turn
Pin position on lever (see rele
-
vant section on attachment).
Press
Select initialization mode:
Initialization mode
Default: MAX
Turn
Code 6
Press , Code
6 blinks.
Turn
MAN
Press to confirm the MAN initialization
mode.
Start initialization:
Initialization
Fail-safe position setting
Progress indicated until
initialization starts
Turn
Code 0
Press , Code
0 blinks.
Turn
Init
Press . The setting of the fail-safe position
AtO or AtC appears.
Keep pressed down for 6 seconds.
Initialization starts after the progress indica
-
tion has stopped.