Data errors
Error codes – Recommended action Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
68
Control parameter
Additional alarm at the fault
alarm output
Control parameter error
Status classification [Maintenance required]
Recommended action Confirm error, perform reset and re-initialize the positioner.
69
Poti parameter
Additional alarm at the fault
alarm output
Parameter error of the digital potentiometer.
Status classification [Maintenance required]
Recommended action Confirm error, perform reset and re-initialize the positioner.
70
Calibration parameter
Additional alarm at the fault
alarm output
Error in the production calibration data. Subsequently, the device
runs on default values.
Status classification [Maintenance required]
Recommended action Return the positioner to SAMSON AG for repair.
71
General parameters Parameter errors that are not critical for the control.
Status classification [Maintenance required]
Recommended action Confirm error.
Check and, if necessary, reset required parameters.
72
Start-up parameters Start-up parameter error
Status classification [Maintenance required]
Recommended action Confirm error, perform reset and re-initialize the positioner.
73
Internal device error 1 Internal device error
Status classification [Maintenance required]
Recommended action Return the positioner to SAMSON AG for repair.
74
HART parameters Parameter errors that are not critical for the control.
Status classification [Maintenance required]
Recommended action Confirm error and perform reset.
EB 8387-3 EN 81
Code list