Samsung AM072BXV Series - MCU Branch Part Setup Error - Connect more Indoor Units than What Is Actually Set up in MCU

Samsung AM072BXV Series
326 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Samsung Electronics 95
4-3-15 MCU branch part setup error – Connect more Indoor units than what is actually set up
in MCU
1. How to check
Check the number of indoor units connected to MCU then readjust the switch for the number of units.

Example of MCU indoor unit setting DIP switch error.
ex) Indoor unit No.5 was connected to branch part C, but DIP switch No.3 (branch part C) is off.
Outdoor Unit PBA
Quantity of
Indoor
Quantity of
MCU
Indoor Unit: 4 MCU: 1
Branch
Outdoor unit
display
Indoorunit
display
Duct, Cassette (1/2 Way),Console, Celing Cassette (4/Mini4 Way) Wall-mounted (NeoForte)
Operation Defrost Timer Fan
Filter/
MPI
Operation Defrost Timer Filter Operation Timer Turbo 24 27
× × × × × × × ×
※ ● : ON : Flash ×: OFF
Judgment
Method
• Occurs when the number of indoor unit installed exceeds that setting in MCU
Cause of
problem
• Number of indoor units exceeds number of indoor units entered on MCU setting
4-3 Appropriate Measures for Different Symptom (cont.)