Samsung Electronics 270
Piping Diagram
Emergency operation for compressor malfunction
Purpose

Concept
Faulty compressors are disabled and turned off.
Control specifications in detail

diagnosed error detection.
Notes
- The performance may degrade if this option is changed.
- Make sure to return the option to the default value after servicing the compressor.

(The SVC V/V must be closed for outdoor units if modules are installed and all the compressors on a single outdoor unit
are disabled.)
Setting Outdoor Seg1 Seg2 Seg3 Seg4 Emergency operation for compressor malfunction
Individual 0 0
0 0 Disabled (Default)
0 1 Set compressor 1 as malfunction state
0 2 Set compressor 2 as malfunction state
7-3 Functions (cont.)
7-3-3-1 Field Setting
7-3-3 Others