Product Specifications
Samsung Electronics 15
■ DVM S2 HP(208~230V)
Type
DVM S2 HP - 208-230V
Model CODE
AM072BXVGFH/AA AM096BXVGFH/AA AM120BXVGFH/AA AM144BXVGFH/AA AM168BXVGFH/AA AM192BXVGFH/AA AM216BXVGFH/AA AM240BXVGFH/AA
Power Supply
Φ, #, V, Hz

      
Mode
-

      
Performance
Ton
TON
6
8 10 12 14 16 18 20
Capacity
(Nominal)
Cooling
Btu/h
72,000
96,000 120,000 144,000 168,000 192,000 216000 240000
Heating
Btu/h
81,000
108,000 135,000 162,000 189,000 216,000 243000 270000
Capacity
(Rated)
Cooling
Btu/h
69000
92000 114000 138000 160000 184000 206000 228000
Heating
Btu/h
77000
103000 129000 154000 180000 206000 232000 258000
Maximum number of connectable indoor units
EA
12
16 20 25 29 33 37 41
Total capacity of the connected indoor
units
Min.
Btu/h
36000
48000 60000 72000 84000 96000 108000 120000
Max.
Btu/h
93600
124800 156000 187200 218400 249600 280800 312000
Power
Power Input
Cooling
kW
5.80
7.10 9.20 11.10 13.80 15.20 18.50 20.90
Heating
5.80 7.60 9.70 11.90 14.40 16.40 19.00 22.50
Current Input
Cooling
A
15.7
19.4 24.8 30.0 37.2 41.0 49.9 56.4
Heating
15.7 20.7 26.2 32.1 38.9 44.3 51.3 60.7
MCA
A
28.0
36.0 40.8 52.6 54.4 60.0 64.0 68.0
MFA (MOP)
A
35.0
40.0 45.0 60.0 60.0 70.0 80.0 80.0
COP
Cooling
(Btu/h)/W
11.9
13.0 12.4 12.4 11.6 12.1 11.1 10.9
Heating
(Btu/h)/W
13.3
13.6 13.3 12.9 12.5 12.6 12.2 11.5
Efciency IEER (AHRI)
W/W
24.20
25.10 24.60 25.70 24.83 26.00 23.70 23.30
Casing Material
Body
-
GI Steel Plate
GI Steel Plate GI Steel Plate GI Steel Plate GI Steel Plate GI Steel Plate GI Steel Plate GI Steel Plate
Base
-
GI Steel Plate
GI Steel Plate GI Steel Plate GI Steel Plate GI Steel Plate GI Steel Plate GI Steel Plate GI Steel Plate
Heat ex-
changer
Type
-
Fin & Tube
Fin & Tube Fin & Tube Fin & Tube Fin & Tube Fin & Tube Fin & Tube Fin & Tube
Material
Fin
-
Al
Al Al Al Al Al Al Al
Tube
-
Cu
Cu Cu Cu Cu Cu Cu Cu
Fin Treatment
-
Anti-corrosion
Anti-corrosion Anti-corrosion Anti-corrosion Anti-corrosion Anti-corrosion Anti-corrosion Anti-corrosion
Compressor
Type
-
Inverter Scroll
Inverter Scroll Inverter Scroll Inverter Scroll Inverter Scroll Inverter Scroll Inverter Scroll Inverter Scroll
Output
kW × n
4.6 x 1
4.6 x 2 4.6 x 2 4.6 x 2 6.45 x 2 6.45 x 2 6.45 x 2 6.45 x 2
Model Name
-

      
Oil
Type
-

      
Initial charge
cc x n
900 x 1
900 x 2 900 x 2 900 x 2 1,100 x 2 1,100 x 2 1,100 x 2 1,100 x 2
Fan
Type
-
Propeller
Propeller Propeller Propeller Propeller Propeller Propeller Propeller
Output x n
W
-
- - - - - - -
Discharge direction
-
Top
Top Top Top Top Top Top Top
Quantity
-
1
2 2 2 2 2 2 2
Air Flow Rate
CMM
158
281 281 288 302 364 377 390
l/s
2633
4683 4683 4800 5033 6067 6283 6500
External Static Pressure Max
mmAq 11
11 11 11 11 8 8 8
Pa
110
110 110 110 110 80 80 80
Fan Motor
Type
-
BLDC Motor
BLDC Motor BLDC Motor BLDC Motor BLDC Motor BLDC Motor BLDC Motor BLDC Motor
Output x n
W x n
630 x 1
620 x 2 620 x 2 620 x 2 620 x 2 630 x 2 630 x 2 630 x 2