Piping Diagram
7-3-2-1 Actuator
7-3-2 Control
Compressor – Capacity control
Purpose

heating mode.
Concept


Control specifications in detail
In cooling case
The capacity of a compressor is controlled by assuming the target pressure during cooling operation.

-
ing that the operating capacity is higher compared to load.
In case that the measured value is higher than the target pressure, raise the operating capacity of the compressor consider-

7-3 Functions (cont.)
The target pressure value is as in the table and the initial setting value is 8.0 kgf/cm2,g. The target pressure is adjusted con-
sidering the rise and fall of the pressure in the pipe. It is calculated using evap in temperature representing the pressure of
-


reaches the setting temperature, maintain the target pressure judging from the evaporated pressure at a certain point. In


temperature is required to be adjusted, it can be adjusted in the main PBA by referring to the installation manual.