EasyManua.ls Logo

Samsung AM072BXV Series - Refrigerant Leakage Error

Samsung AM072BXV Series
326 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Samsung Electronics 117
4-3-36 / Refrigerant leakage error
Outdoor unit display
(Refrigerant leakage judgment before starting)
(When start, refrigerant leakage judgment)
Judgment Method
Before starting : Before compressor starting after system halt 2 minutes

When start : When the high pressure sensor value(cooling 3.1kg/ , heating 2.2kg/ ) is detection continuously for
3 seconds
Cause of
problem
• Refrigerant leakage and shortage

1. Pressure sensor Open/Short error determination method
1) Identifies from when power is supplied or 2 minutes after RESET, and only when set is stopped.
2) An Open/Short error will occur if the input voltage standard range of 0.5V ~ 4.95V is exceeded.
2. Inspection Method
Replace Pressure sensor
Please re-inspect after connecting
the connector to the PBA
No
Yes
Is the
pressure sensor connector connected
to the PBA ?
Refill refrigerant after vacuum
No
Yes
Is there
refrigerant inside the set? (Please check by
connecting the menu folder gauge to the service
valve)
Replace PBA
No
Yes
Out of the PBA Pressure
sensor terminals, is there voltage between
pins 3 and 4 5V?

4-3 Appropriate Measures for Different Symptom (cont.)

Table of Contents

Related product manuals