Piping Diagram
Samsung Electronics 271
Cooling capacity correction
▪ Purpose
Control the cooling performance.
▪ Concept
▪ Control specifications in detail
-
- See "Compressor capacity control" for details on compressor operation specifications.
▪ Notes
- The performance may degrade if this option is changed.
- Make sure to return the option to the default value after servicing the compressor.
(The SVC V/V must be closed for outdoor units if modules are installed and all the compressors on a single
outdoor unit are disabled.)
Input unit Seg1 Seg2 Seg3 Seg4 Temperature(℃ )
Main 0 1
0 0 7-9
0 1 5 - 7 (default)
0 2 9 - 11
0 3 10 - 12
0 4 11 - 13
0 5 12 - 14
0 6 13 - 15