EasyManua.ls Logo

Samsung AM072BXV Series - Page 278

Samsung AM072BXV Series
326 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Samsung Electronics 272
Piping Diagram
Heating capacity correction
Purpose
Control the heating performance.
Concept
The Target high pressure is changed to control the pressure in heating mode.
Control specifications in detail
- The high pressure for outdoor units and the compressor operation frequency are controlled according to the Target high

- See "Compressor capacity control" for details on compressor operation specifications.
Notes
- 

Input unit Seg1 Seg2 Seg3 Seg4 Pressure(kgf/cm2,g)
Main 0 2
0 0 30 (default)
0 1 25
0 2 26
0 3 27
0 4 28
0 5 29
0 6 31
0 7 32
0 8 33
7-3 Functions (cont.)
7-3-3-1 Field Setting (cont.)
7-3-3 Others (cont.)