Samsung Electronics 234
Piping Diagram
Safety Start – Normal Start
Purpose

Concept

Control specifications in detail
- Condition(s) required to enter Normal Start mode : None of the conditions required to enter Quick Start mode are satisfied.


- Condition(s) required to enter Normal Operation mode : [ A or B ]
 


- Condition(s) required to close Cold Operation mode: [ A or B ]
A. A maximum of 30 min has elapsed B. DSH > 15 K
7-3 Functions (cont.)
7-3-2-2 Start-up modes (cont.)
7-3-2 Control (cont.)