EasyManua.ls Logo

Samsung AM072BXV Series - Page 247

Samsung AM072BXV Series
326 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Piping Diagram
Samsung Electronics 241
Main heating operation
Purpose

Control specifications in detail
Actuator - Main Heating
Compressor COMP
Operation
Target high pressure control
(default : 30kgf/cm2,g)
Range 
Outdoor Fan Motor OFM
Operation

(default : 7.5-8.7kgf/cm2,g)
Range 0-39step (0-1300rpm)
Electronic Expansion Valve – Main (Main EEV) E_M
Operation
*Superheat control
(default: SH 2 K)
Range 125-2000step
Electronic Expansion Valve – EVI (EVI EEV) E_EVI
Operation
* EVI Superheat control
(default: SH 2 K)
Range 0-480step
 V_4W Operation On
Solenoid Valve – EVI Bypass V_EB Operation
On (Open):
T_a > 15
Off (Close):
T_a < 10
Solenoid Valve – EVI V_EVI Operation On (Open)
Solenoid Valve – Hot Gas Bypass V_HG Operation Off (Close)
Solenoid Valve – Accumulator Oil Return V_AR Operation On (Open)
Solenoid Valve – Hot Gas Bypass 2 (HR Only) V_HG2 Operation Off (Close)
Solenoid Valve – Main EEV (HR Only) V_ME Operation Off (Close)
Solenoid Valve – Main Cooling (HR Only) V_MC Operation Off (Close)
7-3 Functions (cont.)
7-3-2-3 Normal operation modes (cont.)
7-3-2 Control (cont.)

Table of Contents

Related product manuals