Piping Diagram
Samsung Electronics 247
Oil return operation
▪ Purpose
Perform oil return after a specified amount of time has elapsed in order to prevent an insufficient amount of oil in compressors.
▪ Concept
piping.
▪ Control specifications in detail
-
lected to outdoor unit by starting oil collecting operation.
-
ing condition (# of compressor in operation and operating frequency). Once defrosting operation operate for more than 3 minutes
Actuator Oil return Operation
Capacity of compressor Current capacity + additional capacity
Outdoor EEV Normal control
Outdoor Fan Normal control
Indoor EEV
Operating indoor units Higher step of [400(C)/300(H) or Current step]
Stopped indoor units 400(C)/300(H)
Indoor Fan Normal control
Time 3min(C) / 6min(H)
*Additional capacity = Compensation capacity of stop units
* EEV step can be varied by cycle condition.
7-3 Functions (cont.)
7-3-2-4 Special operation modes (cont.)
7-3-2 Control (cont.)