Samsung Electronics 256
Piping Diagram
DSH (Discharge Super Heat) protection
Purpose
Prevent liquid compression to protect the system and compressors.
Concept
The compressor Suction Super Heat (SH) is raised to increase the DSH.
- DSH = Compressor discharge temp. – High pressure saturation temp.
- The compressor discharge temperature is defined during DSH protection control :
Min { Max(Tdis_comp1, Ttop_comp1), Max(Tdis_comp2, Ttop_comp2) }
Control specifications in detail

Enthalpy
Pressure
Ph-Diagram
After DSH protection
Befo re DSH protection
DSH increase
SH increase
Normal Operation
10
15
20
DSH (K)
First heating release : the target SH is 3 K if in this state for 30 sec
Second heating release : SH release occurs 2 min after the first release

First cooling release : the target SH is 3 K if in this state for 30 sec
Second cooling release : SH release occurs 2 min after the first release if
the DSH is above 10 K
- If in this state for 30 sec,
Cooling : Indoor unit EEV Target SH 6 K
Heating : Main EEV Target SH 6 K