Samsung Electronics 258
Piping Diagram
Maximum current limit (total)
Purpose
Prevent operation if the electric current capacity is exceeded.
Concept
- 
the maximum electric current.
- Outdoor unit current = Compressor current + Outdoor fan current (= CT1 + CT2)
CT1 = Compressor 1 current + Fan current
- Maximum outdoor unit current = Maximum current of the system x Set value
- Set value : 50-100% (default 100%). The value can be set from outdoor unit options or the upper-level controller.

Control specifications in detail




if the outdoor unit current at present is higher than the maximum current.
7-3 Functions (cont.)