Piping Diagram
Silent mode for night-time
▪ Purpose
▪ Concept
-
(Noise level: Level 1 > Level 2 > Level 3)
- External contact : Configure this option if using an interface module (MIM-B14).
Silent mode turns on if the external contact is on.
▪ Control specifications in detail
- The maximum compressor frequency and outdoor fan RPM decrease according to the specified level.
- Silent mode automatically turns on according to the day/night temperature pattern if Auto mode is on.
▪ Notes
- Noise level according to the specified silent mode LEVEL.
Input unit Seg1 Seg2 Seg3 Seg4 Silent mode for night - time
Main 0 7
0 0 Disabled (default)
0 1 LEVEL 1 / Auto
0 2 LEVEL 2 / Auto
0 3 LEVEL 3 / Auto
0 4 LEVEL 1 / External contact
0 5 LEVEL 2 / External contact
0 6 LEVEL 3 / External contact
0 7 LEVEL 1
0 8 LEVEL 2
0 9 LEVEL 3
Silent mode Noise level (dB)
Disabled SPEC
LEVEL 1 SPEC – 1/3*(SPEC-49)
LEVEL 2 SPEC – 2/3*(SPEC-49)
LEVEL 3 49
7-3 Functions (cont.)
7-3-3-1 Field Setting (cont.)
7-3-3 Others (cont.)