Piping Diagram
Long-piping condition setting
Purpose

Concept
- 
a long piping condition.
Control specifications in detail
- In heating mode, the initial EEV opening degree increases.

(see "Main EEV control" for details on EEV control).

(see "Compressor capacity control" for details).
- In cooling mode, EVI bypass mode turns on (see "EVI EEV control" for details).
Notes
- Incorrect settings may seriously damage the system.
- Setting is unnecessary if high-head condition is set.
Input unit Seg1 Seg2 Seg3 Seg4 Long-piping condition setting
Main 0 9
0 0 Disabled (default)
0 1
Level 1
(When equivalent length of farthest indoor unit

0 2
Level 2
(When equivalent length of farthest indoor unit
from the outdoor unit is over 170m)
7-3 Functions (cont.)
7-3-3-1 Field Setting (cont.)
7-3-3 Others (cont.)