Samsung Electronics 282
Piping Diagram
7-3 Functions (cont.)
7-3-3-1 Field Setting (cont.)
7-3-3 Others (cont.)
Snow accumulation prevention control
Purpose

Concept

via the outdoor temperature.




the outdoor fans operate in 3 step for 10 sec and then continue operation in a higher step for 50 sec.
Input unit Seg1 Seg2 Seg3 Seg4 
Main 1 4
0 0 Enabled (default)
0 1 Disabled
Notes

- Outdoor fans may be turned on by this feature during servicing. Careful attention is required.
Speed operation
Purpose

Concept
-The cooling or heating speed is increased by raising the compressor frequency increase speed.

- The frequency and increase speed are increased in Safety Start mode.
- The control speed is improved by changing the interval to control the target heating pressure to 20 sec from 40 sec.
Input unit Seg1 Seg2 Seg3 Seg4 Speed operation
Main 1 7
0 0 Disabled (default)
0 1 Enabled
Notes

Max capacity restriction
Purpose
Prevent an excessive increase of compressor performance compared to the capacity of indoor units (default option).
Concept
The maximum capacity for outdoor units is restricted taking into account the capacity of indoor units and the outdoor tem-
perature.

- The maximum operation capacity is restricted, taking into account the capacity of indoor units, set fan speed,


high pressures.
Input unit Seg1 Seg2 Seg3 Seg4 Max capacity restriction
Main 1 8
0 0 Enabled (default)
0 1 Disabled