Key Options
- Outdoor unit Address setting
Order Display Description
1
Normal display : "Ad 00"
Outdoor address is not set : "od nd"
2
Press and hold simultaneously K1, K2 to enter the setting mode.
(When entering the setting mode, letters are displayed as the left : "od 00")
- od means Outdoor unit
3
Press the K4 button shortly : Setting a 1-digit
4
Press the K1 button shortly : Setting a indoor quantity

Order Display Description
1
When entering the Indoor setting mode, letters are displayed as the left : "id 00"
- id means Indoor unit
2
Manual setting mode (Default)
- Press the K2 button shortly : Setting a 10-digit
- Press the K4 button shortly : Setting a 1-digit
Automatic setting mode (Option)
Press and hold the K4 button : It is changed to the automatic setting mode, and displays the
number of the connected indoor unit.
(Ex. If 10 indoor units are connected, "id 10" is indicated.)
- If press the K2, K4 button shortly in the automatic setting mode, it is changed to the manual
mode. (
Ex. If 10 is indicated and press the K4 button, 11 is indicated and changed to the manual
mode.)
3
Heat recovery model : Setting Mcu address.
- Press the K1 button shortly : Setting a MCU address
Heat Pump model : Confirm settings
- Press and hold the K2 button
- All settings are saved

Cancel settings

8-3 Outdoor unit option switch settings (cont.)