Samsung Electronics 288
Key Options
8-4 How to check the view mode using a tact switch (cont.)
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Emergency opera-
tion for compressor
malfunction
Individual 0 0
0 0 Disabled (Factory default)
-
sors are set as malfunction state.
0 1 Set compressor 1 as malfunction state
0 2 Set compressor 2 as malfunction state
Capcity correction
for cooling
Main 0 1
0 0 7-9 (Factory default)
Targeted evaporation temperature
set, discharged air temperature of the
0 1 5-7
0 2 9-11
0 3 10-12
0 4 11-13
0 5 12-14
0 6 13-15
Capcity correction
for heating
Main 0 2
0 0 3.0 (Factory default)
Targeted high pressure [MPa].
-
charged air temperature of the indoor
0 1 2.5
0 2 2.6
0 3 2.7
0 4 2.8
0 5 2.9
0 6 3.1
0 7 3.2
0 8 3.3
Current
restriction rate
Individual 0 3
0 0 100% (Factory default)
When restriction option is set,
cooling and heating
performance may decrease
0 1 95 %
0 2 90 %
0 3 85 %
0 4 80 %
0 5 75 %
0 6 70 %
0 7 65 %
0 8 60 %
0 9 55 %
1 0 50 %
1 1 No restriction
Oil collection interval Main 0 4
0 0 Factory default
0 1 Shorten the interval by 1/2
Temperature to
trigger defrost
operation
Main 0 5
0 0 Factory default
0 1
being installed in humid area such as
near river or lake
Fan speed correction
for outdoor unit
Individual 0 6 0 0 Factory default
Silent mode Main 0 7
0 0 Disabled (Factory default)
Enable the silent mode for
night-time in cooling mode (Itoperates
automatically depending on the tem-
perrature.)
ineterface module(MIM-B14) is used,
entering the silent mode is available
-
ing mode.
0 1 LEVEL 1 / Auto
0 2 LEVEL 2 / Auto
0 3 LEVEL 3 / Auto
0 4 LEVEL 4 / External contact
0 5 LEVEL 5 / External contact
0 6 LEVEL 6 / External contact
0 7 LEVEL 1
0 8 LEVEL 2
0 9 LEVEL 3
AM080/100/120/140/160/180/200/220/240/260AXVGGH, AM080/100/120/140/160/180/200/220/240/260AXVGGR,
AM080/100/120/140/160/180/200/220/240/260AXVAGH, AM100/120/140/160/180AXVDGH